Armored 33KV Underground Power Cable Price and Specifications

APPLICATIONS:
The cables are designed for distribution of electrical power with nominal voltage Uo/U 19/33KV and frequency 50Hz. It is used to transmit and distribute power in power transmission and distribution system of 33kV or lower. It is generally applied to the fields including power, construction, mines, metallurgy, petrochemical industry and communication in complete replace of oil immersed paper insulated power cable and in partial replace of PVC insulated power cable.

STANDARD:
BS 6622
BS 7835 (LSZH Version)

228bed8ed81af66514af6c4f8f67a8cd.jpg

CONSTRUCTION:
Conductor: Plain annealed copper or aluminium complying with IEC 60228/BS 6360. Copper conductors shall be stranded and aluminium conductors shall be either solid or stranded.
Conductor Screen: Extruded layer of semi-conducting cross-linkable compound is applied over the conductor and shall cover the surface completely. The minimum thickness is 0.3mm and the maximum resistivity shall not exceed 500 Ohm-m at 90°C.
Insulation: Insulation is of cross-linked polyethylene compound XLPE (GP8) conforming to BS 7655-1.3 or EPR (GP7), conforming to BS 7655-1.2.

TABLE 1. INSULATION THICKNESS:


Nom. Cross Section AreaInsulation Thickness at Nom. Voltage
19/33KV(Um=36KV)
mm²mm
70 – 1858.0
2408.0
3008.0
4008.0
Above 5008.0


52ce0c1dd13dbff74ee143944a1847a6.jpg

Insulaton Screen: Extruded layer of semi-conducting cross-linkable compound is applied over the insulation. The extruded semi-conducting layer shall consist of bonded or cold strippable semi-conducting compound capable of removal for jointing or terminating. As an option, a semi-conducting tape may be applied over the extruded semi-conducting layer as a bedding for the metallic layer. The minimum thickness is 0.3 mm and the maximum resistivity is 500 Ohm-m at 90°C. The screen is tightly fitted to the insulation to exclude all air voids and can be easily hand stripped on site. Inner Covering; Fillers: For cables with a collective metallic layer or cables with a metallic layer over each individual cores with additional collective metallic layers, semi-conducting inner covering and fillers shall be applied over the laid up cores. The inner covering is made of non hygroscopic material, except if the cable is to be made longitudinally watertight. The inner covering shall be extruded or lapped.
The approximate thickness of extruded inner coverings is given in Table 2:


TABLE 2. APPROXIMATE THICKNESS OF EXTRUDED INNER COVERINGS


Ficititous Diameter over Laid Up Cores;Approx. Thickness of Extruded Inner Covering;
mm;mm
>;<;
-251.0
25351.2
35451.4
45601.6
60801.8
80-2.0


766abeb843fc2c9f4270f0b03393a1e3.jpg

Metallic Layer: The metallic layer shall be applied over each core or applied as a collective screen. The metallic screen shall consist of either copper tapes or a concentric layer of copper wires or a combination of tapes and wires. The metallic layer provides an earth fault current path, capable of withstanding fault current to earth of 1000A for one second at maximum temperature 160°C. Copper wires are applied over the conducting water blocking layer with a minimum diameter of 0.5mm. And over the copper wires, copper tape with minimum thickness of 0.1mm can be applied helically with overlap. Total cross section of copper wire screen is shown in table 3.

TABLE 3. MINIMUM TOTAL CROSS SECTION OF COPPER WIRE SCREEN; DC RESISTANCE OF THE SCREEN


Nominal Cross-Section Area of CableMinimum Cross-Section of Copper Wire Screen AreaDC Resistance of the Copper Wire Screen
mm²mm²mm
up to;120161.06
150-300250.72
400-630350.51


Separation Sheath (for armoured cable): The separation sheath comprises a layer of extruded PVC, PE or LSZH. The nominal thickness is calculated by 0.02Du + 0.6mm where Du is the fictitious diameter under the sheath in mm. The nominal separation sheath thickness shall not be less than 1.2mm.
Armour (for armoured cable): The armour consists of galvanized steel wire applied over the inner covering with diameter specified as in Table 4.

TABLE 4. ARMOUR WIRE DIAMETER


Fictitiious Diameter under the ArmourArmour Wire Diameter
mmmm
><
-251.6
25352.0
35602.5
60-3.15


Over Sheath: Overall sheath comprises a layer of extruded either PVC type 9 conforming to BS 7665-4.2 or MDPE type TS2 conforming to BS 7655-10.1; LSZH can be offered as an option. The over sheath is normally black in colour. When a DC voltage test is to be performed on the over sheath, a semi-conducting layer such as graphite coating shall be applied over the surface of the extruded over sheath. The nominal over sheath thickness is calculated by 0.035D+1 where D is the diameter immediately under the over sheath in mm. For cables with the over sheath not applied over the armour, the nominal over sheath thickness shall not be less than 1.4mm. And for cables with over sheath applied over the armour, the nominal over sheath thickness shall not be less than 1.8mm.

PHYSICAL PROPERTIES:
Operating Temperature: up to 90°C
Temperature Range: -5°C ( PVC or LSZH sheath ); -20°C ( PE sheath ) Short Circuit Temperature: 250°C (short circuit duration up to 5 seconds) Bending Radius: 12 x OD DIMENSIONAL DATA:


Nom. Cross- Section 
Area
Nom. Insulation 
Thickness
Copper Tape 
Screen Area
Nom.Bedding 
Thickness
Nom. Armour 
Wire Diameter
Nom.Sheath 
Thickness
Approx. Overall 
Diameter
Approx. Weight
CUAL
mm²mmmm²mmmmmmmmkg/km
508.06.71.83.153.479.0106209680
708.07.11.83.153.582.51184010440
958.07.51.93.153.686.41320011350
1208.07.92.03.153.789.91452012190
1508.08.22.03.153.893.61607013280
1858.08.62.13.153.997.31771014090
2408.09.22.23.154.1103.22037015460
3008.09.72.33.154.3108.22298017210
4008.010.32.43.154.5116.82748019450

0086-371-68665329

(You can contact us through online message or business connection, or call our national sales hotline.)

OUR SERVICE