0.6/1KV LSZH Sheath Power Cable

APPLICATION:
These XLPE insulated and LSZH sheathed cables are generally used for fixed installation. Suitable for building wiring, especially in areas where smoke and fume emissions may cause a potential threat to life but not for burial in the ground, either directly or in ducts.

c2e29294df80655e60e0aa351fdef1e7.jpg

STANDARD
Basic design to BS 8573:2012

FIRE PERFORMANCE


Flame Retardance (Single Vertical Wire Test)BS EN 60332-1-2:2004
Reduced Fire Propagation  (Vertically-mounted bundled wires; cable test)BS EN 60332-3-24:2009 (cat. C)
Halogen FreeBS EN 50267-2-1
Minimum Smoke EmissionBS EN 61034-2
Spark TestBS EN 62230

 


0.6/1KV LSZH Sheath power cable

VOLTAGE RATING:
600/1000V

CABLE CONSTRUCTION:
Conductor: Annealed copper conductor, strand according to BS EN 60228 class 2.

Insulation: XLPE type GP8 according to BS 7655-1.3. HEPR type GP6 according to BS 7655-1.2, or crosslinked polyolefi n material type EI 5 according to BS EN 50363-5 can be offered as option.

Inner Covering option: The laid up cores may be coverd by an optional extrued inner covering or separating tape. It shall be possible to separate the cores easily.

Outer Sheath: Thermoplastic LSZH type LTS 4 according to BS 7655-6.1.

Outer Sheath option: UV resistance, hydrocarbon resistance, oil resistance, anti rodent and anti termite properties can be offered as option.

COLOUR CODE:
Insulation Colour:

Blue, brown black and grey,

Alternatively, green-and-yellow, brown, black, grey

Sheath Colour: Black, other colours can be offered upon request.

PHYSICAL AND THERMAL PROPERTIES
Maximum temperature range during operation (XLPE): 90°C Maximum short circuit temperature (5 Seconds): 250°C Minimum bending radius:

Circular copper conductors(up to 25mm2): 4 x Overall Diameter

Circular copper conductors(above 25mm2): 6 x Overall Diameter

Shaped copper conductors: 8 x Overall Diameter

CONSTRUCTION PARAMETERS
 

ConductorNominal Insulation ThicknessNominal Sheath Thickness
No.of Coresx Cross SectionClass of Conductor
No.xmm2
mmmm
4x1.520.71.8
4x2.520.71.8
4x4.020.71.8
4x6.020.71.8
4x1020.71.8
4x1620.71.8
4x2520.91.8
4x3520.91.8
4x5021.01.8
4x7021.12.0
4x9521.12.1
4x12021.22.3

 


0086-371-68665329

(You can contact us through online message or business connection, or call our national sales hotline.)

OUR SERVICE

COMMODITY PRICE

Get the minimum offer free of charge, please fill in the following information to tell us (confidential information, not open to the public.)

Henan Jiapu cable co., ltd

E-MAIL:info@jiapucable.com

ADD:
No.18 Building, The National University Science Park of Henan Province, No.283 Xisanhuan Road, Zhengzhou, China.

7×24 Online

Hello, may I help you?

GET LATEST PRICE

CHAT